Housing material |
|
Housing |
Polyamide PA6.6 |
Weight |
|
Net |
0,23 kg |
Ambient temperature |
-15 ... 40 °C |
Degree of protection |
IP20 |
Mechanical life |
|
operating cycles |
10 x 106 |
Contact material |
AgSnO2 |
Mounting method |
Mounting rail 35mm according to DIN EN 60715 TH35 |
Connection |
Connection terminals |
Length of control cable |
|
With conductor cross-section 0.75mm2 |
1000 m |
Safety contacts 13/14, 23/24, 33/34 |
|
Number of safety contacts |
3 |
Auxiliary contacts 41/42 |
|
Number of auxiliary contacts |
1 |
Electrical connection ratings
Operating voltage |
|
AC/DC |
24 V -10% ... +10% |
Rated insulation voltage Ui |
|
AC |
250 V |
Rated impulse withstand voltage Uimp |
|
Leakage path/air gaps |
4 kV |
Overvoltage category according to IEC EN 60664-1 |
3 |
Reverse polarity protection |
|
On version UB =24V DC |
|
Rated supply frequency |
50 ... 60 Hz |
Power consumption |
|
at 24 V DC |
2,3 W |
Degree of contamination (external, according to EN 60947-1) |
2 |
Connection cross-section |
0,14 ... 2,5 mm² |
Test voltage |
|
Control system/contacts |
2,5 kV |
Control voltage |
|
On S11 |
24 V 18,6 ... 26 V Start button |
Control current |
|
S11...S14 |
60 mA |
LED indicator |
2 status displays (green) for relays K1 and K2 |
Safety contacts 13/14, 23/24, 33/34 |
|
Type of output |
|
NO |
Relay contacts, floating and positively driven (redundant) |
Switching voltage |
|
DC |
max.24 V |
AC |
max.250 V |
Switching current |
|
at 24V |
min.5 mA |
Cumulative current |
max.15 A For all contacts |
Fusing |
|
External contact fuses (safety circuit) according to IEC 60269-1 |
10A gG |
Utilization category according to EN 60947-5-1 |
|
AC-15 |
3A , 250V |
DC-13 |
3A , 24V |
AC-12 |
8A ohmic load, 250V |
DC-12 |
8 A ohm resistive load, 40 V |
Breaking capacity according to UL |
8A 250V AC / 3A 24V DC per contact |
Auxiliary contacts 41/42 |
|
Type of output |
|
NC |
Relay contacts, floating |
Utilization category according to EN 60947-5-1 |
|
AC-12 |
2A ohmic load, 250V |
DC-12 |
2 A ohm resistive load, 40V |
Breaking capacity according to UL |
2A, 250V AC / 2A, 24V DC per contact |
Other
In compliance with |
EN ISO 13849-1: 2015; EN 62061: 2005 + AC: 2010 + A1: 2013 + A2: 2015; EN 50581: 2012 (RoHS) |
Reliability values according to EN ISO 13849-1
Performance Level |
PL e |
Category |
4 |
PFHD |
1.2 x 10-8 |
Number of switching cycles |
|
≤ 1 A at 24 V DC |
max.350000 1/Jahr |
≤ 0.1 A at 24 V DC |
max.500000 1/Jahr |
≤ 2 A at 24 V DC |
max.100000 1/Jahr |
Mission time |