Photoelectric distance sensor


Product characteristics

Communication interface

IO-Link

Laser protection class

2

Housing

rectangular

Dimensions [mm]

59 x 42 x 52

Electrical data

Operating voltage [V]

18...30 DC

Current consumption [mA]

< 150

Protection class

III

Reverse polarity protection

yes

Typ. lifetime [h]

50000

Inputs / outputs

Number of inputs and outputs

Number of digital outputs: 2; Number of analogue outputs: 1

Outputs

Total number of outputs

2

Electrical design

PNP

Number of digital outputs

2

Output function

normally open / normally closed; (programmable)

Max. current load per output [mA]

200

Number of analogue outputs

1

Analogue current output [mA]

4...20; (scalable IEC 61131-2)

Max. load [Ω]

250

Analogue voltage output [V]

0...10; (scalable IEC 61131-2)

Min. load resistance [Ω]

5000

Short-circuit protection

yes

Type of short-circuit protection

pulsed

Overload protection

yes

Detection zone

Max. light spot width [mm]

15

Max. light spot height [mm]

15

Light spot dimensions refer to

10 m

Background suppression [m]

10...100

Measuring/setting range

Measuring range [m]

0.2...10; (white paper 200 x 200 mm 90% remission)

Sampling rate [Hz]

1...33

Interfaces

Communication interface

IO-Link

Transmission type

COM2 (38.4 kBaud)

IO-Link revision

1.1

SDCI standard

IEC 61131-9

IO-Link device ID

806 d / 00 03 29h

Profiles

Smart Sensor: Device Identification; Device Diagnosis; Device Teach Channel; Binary Data Channel; Process Data Variable

SIO mode

yes

Required master port type

A

Process data analogue

2

Process data binary

2

Min. process cycle time [ms]

6

Operating conditions

Ambient temperature [°C]

-10...60

Protection

IP 67

Tests / approvals

EMC

EN 60947-5-2

Laser protection class

2

Notes on laser protection

Caution:

laser light

Power:

<= 4,0 mW

Wave length:

650 nm

pulse:

1,3 ns

Do not stare into beam.

Avoid exposure to the laser light.

laser class:

2

EN / IEC60825-1:2007

EN / IEC60825-1:2014

Complies with 21 CFR 1040 except for deviations pursuant to Laser Notice No. 50, dated June 2007.

MTTF [years]

107

Mechanical data

Weight [g]

312

Housing

rectangular

Dimensions [mm]

59 x 42 x 52

Materials

housing: diecast zinc; front lens: glass; LED window: PC

Lens alignment

side lens

Displays / operating elements

Display

switching status

2 x LED, yellow

operation

LED, green

distance value, programming

alphanumeric display, 4-digit

Accessories

Accessories (optional)

Protective cover, E21133

Remarks

Remarks

operating voltage "supply class 2" according to cULus

Pack quantity

1 pcs.

Electrical connection

Connection

Connector: 1 x M12

Other data

Parameter

Setting range

Factory setting

Uni

mm, m, inch

mm

OU1

Hno, Hnc, Fno, Fnc

Hno

SP1

200...9999

1000

nSP1

200...9999

800

FSP1

200...9999

1200

OU2

Hno, Hnc, Fno, Fnc, I, U

I

SP2

200...9999

2000

nSP2

200...9999

1800

FSP2

200...9999

2200

ASP

0...9999

0

AEP

0...9999

9999

rATE [Hz]

1...33

15

dS1

0...0.1...5

0

dr1

0...0.1...5

0

dS2

0...0.1...5

0

dr2

0...0.1...5

0

dFo

0...0.1...5

0

dIS

d1...3; rd1...3; OFF

d3

repeatability/accuracy

repeatability of the measured values

Accuracy

white (90 % remission)

grey (18 % remission)

white (90 % remission)

grey (18 % remission)

200...1000 mm

± 4.5 mm

± 6.0 mm

± 15.0 mm

± 16.0 mm

1000...2000 mm

± 5.0 mm

±8.0 mm

± 15.0 mm

± 18.0 mm

2000...4000 mm

± 16.0 mm

±19.0 mm

± 25.0 mm

± 30.0 mm

4000...6000 mm

± 24.0 mm

± 33.0 mm

± 35.0 mm

± 45.0 mm

6000...10000 mm

± 50.0 mm

-

± 65.0 mm

-

Sampling rate

15 Hz

Extraneous light on the object

< 40 klx

repeatability/accuracy

repeatability of the measured values

Accuracy

white (90 % remission)

grey (18 % remission)

white (90 % remission)

grey (18 % remission)

200...2000 mm

± 14.0 mm

± 14.0 mm

± 24.0 mm

± 24.0 mm

2000...4000 mm

± 25.0 mm

± 30.0 mm

± 35.0 mm

± 40 mm

4000...6000 mm

± 31.0 mm

±45.0 mm

± 41.0 mm

± 55.0 mm

6000...10000 mm

± 60.0 mm

-

± 70.0 mm

-

Sampling rate

15 Hz

Extraneous light on the object

< 40...100 klx

Range on black object (6 % remission)

<= 4000 klx

The values apply at

constant ambient conditions

23 °C / 960 hPa

minimum power-on time in minutes

10